Part 9 - Controls
Description
Value
Menu
Setting
Default
Sub-Menu
Parameter
0 = Fixed Outlet Temperature 1 = Basic Temp. Control 2 = Indoor Temp. Reset 3 = Outdoor Temp. Reset 4 = Indoor and Outdoor Temp. Reset
See Table 29 and F. Type of Temperature Control for details.
Type of Temperature Control
3
5 2 1
Slope of Outdoor Reset Curve
0.2 - 3.5
1.3
5 2 2
See graph and description of Parameter 422.
-12 - +12 (when 4.2.0 = 0) -25 - +25 (when 4.2.0 = 1)
Parallel Shift of Reset Curve
0
5 2 3
See description of Parameter 423.
2 if Parameter 4.2.0 = 0 4 if Parameter 4.2.0 = 1
Room Sensor In uence
0 - 20
5 2 4
Adjusts the in uence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler target temperature as the indoor temperature drops below room setpoint. Only applicable when using an optional NTI Room Sensor and when 5.2.1 = 2 or 4. 179 5.2.5 sets the allowable boiler operating temperature range for Zone 2 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. 95 5.2.6 sets the allowable boiler operating temperature range for Zone 2 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. MAXIMUM Temperature Setting 68 - 179 °F MINIMUM Temperature Setting 68 - 179 °F
5 2 5
5 2 6
5 3 ZONE 2 DIAGNOSTICS 5 3 0 Room Temperature
Read only Read only
Only applicable when using an NTI room sensor
Room Temperature Setpoint
5 3 1 5 3 4
Heat Call
0 = OFF, 1 = ON (Read only)
5 7 ZONE 2 REGULATION PARAMETERS
See description of Parameter 475.
Auto Boost
0 = OFF, 1 = ON
0
5 7 5
6 ZONE 3 PARAMETERS 6 0 ZONE 3 TEMPERATURE SETTINGS 6 0 0 Temperature Day
50 - 86 °F 32 - 86 °F 68 - 179 °F 68 - 179 °F
66 Only applicable when using an NTI room sensor
Temperature Night
61
6 0 1
179 Parameter 6.2.0 = 1 120 Parameter 6.2.0 = 0
Fixed Temperature
6 0 2
Only applicable when using an NTI room sensor - Changes all zones
Zone Freeze Protection Temperature
36 - 59 °F
41
6 0 3
6 1 SUMMER/WINTER CHANGEOVER 6 1 0 S/W function activation
0 = OFF, 1 = ON
1
S/W temperature threshold
50 - 86 °F
68
6 1 1
S/W delay time
0 - 300 minutes
60
6 1 2
6 2 ZONE 3 SETTINGS
This parameter determines the starting boiler target temperature when using Basic Temp. Control (6.2.1 = 1)
Temperature Range
0 - 1
1
6 2 0
0 = Fixed Outlet Temperature 1 = Basic Temp. Control 2 = Indoor Temp. Reset 3 = Outdoor Temp. Reset 4 = Indoor and Outdoor Temp. Reset
See Table 29 and F. Type of Temperature Control for details.
Type of Temperature Control
3
6 2 1
Slope of Outdoor Reset Curve
0.2 - 3.5
1.3
6 2 2
See graph and description of Parameter 422.
72