NTI INSTALLATION MANUALS
Part 6 - Installing the Condensate Drain
NOTES: 1. Condensate line must be pitched at least ¼” per foot to properly drain. If this cannot be done, or a very long length of condensate hose is used, increase the condensate line to a minimum of 1” ID and place a tee in the line after the condensate neutralizer to properly reduce vacuum lock in the drain line. 2. PVC or CPVC pipe should be the only material used for condensate line. Steel, brass, copper, and other metals will be subject to corrosion or deterioration. 3. A frozen condensate line could result in a blocked vent condition. It is very important to protect the condensate line from freezing temperatures or any type of blockage. In installations that may encounter sustained freezing conditions, the use of heat tape is recommended to avoid freezing of the condensate line. It is also recommended to bush up the condensate line size to 1” and terminate condensate discharge as close to the unit as possible. Longer condensate runs are more prone to freezing. Damages due to frozen or blocked condensate lines ARE NOT covered by warranty. 4. Support of the condensate line may be necessary to avoid blockage of the condensate ow. 5. To allow proper drainage on longer horizontal condensate runs, tubing size may need to increase to 1” and a second line vent may be required. NOTE: To clean out condensate trap, see Maintenance section.
CONDENSATE REMOVAL TO FLOOR DRAIN) CONDENSATE PIPING (SUGGESTED SETUP FOR
BOILER
PROVIDED FLEXIBLE CONDENSATE HOSE
LOOSE FITTING 1" X 3/4" PVC CONNECTION FOR VACUUM BREAK AND OVERFLOW EXAMPLE:
PIPE REDUCER - SWEAT
PIPE HANGERS RECOMMENDED BE USED TO SUPPORT
HORIZONTAL PIPING VERTICAL OR
RECOMMENDED
LP-723-A 06/24/20
3/4" PVC PIPE
HORIZONTAL LINES RECOMMENDED
BE INSTALLED WITH A PITCH
OF 1/4" PER FOOT
EXISTING DRAIN
RECOMMENDED CONDENSATE NEUTRALIZER
CONDENSATE PIPING WITH PUMP (SUGGESTED SETUP FOR CONDENSATE
REMOVAL TO OUTSIDE SOURCE)
TO OUTSIDE
OR DRAIN
BOILER
PROVIDED FLEXIBLE CONDENSATE HOSE
EXAMPLE: LOOSE FITING BREAK AND OVERFLOW RECOMMENDED: CONNECTION FOR VACUUM
1" x 3/4" PVC PIPE REDUCER - SWEAT
RECOMMENDED:
NEUTRALIZER CONDENSATE
RECOMMENDED: 3/4" PVC PIPE SWEAT
CONNECTIONS THROUGHOUT
PIPING SUPPORTS RECOMMENDED:
06/24/20 LP-723-B
HORIZONTAL LINES MUST RECOMMENDED: BE INSTALLED WITH A PITCH
554200 LITTLE GIANT CONDENSATE PUMP
OF 1/4" PER FOOT
Figure 58 - Condensate Piping Suggestions
52
Made with FlippingBook - Online magazine maker