Part 9 - Controls
H. Automatic Temperature Control (AUTO) The Automatic Temperature Control (AUTO) function allows the boiler to automatically adjust the target temperature of each heating zone to adapt to outdoor and/or indoor temperature conditions and/or heat demand cycles. Select the type of Temperature Control via parameters 4.2.1 (Zone 1), 5.2.1 (Zone 2), or 6.2.1 (Zone 3). The default setting is 3 (Outdoor Reset) for parameter 4.2.1 and 1 for parameters 5.2.1 e 6.2.1 . See Table 29. NOTE: Automatic Temperature Control is only possible when the AUTO function is turned ON. To activate the AUTO Function, set to “ON” via the User Menu, or set parameter 2.2.4 = 1 via the technical menu. In order for the boiler to detect changes in room temperature it is necessary to install an NTI Room Sensor. Other thermostats (not NTI) can only switch the boiler ON and OFF. NOTICE Parameters of Automatic CH Temperature Control Example: Zone 1 - 400 Level Parameters NOTE: Zones 2 and 3 can be changed in the equivalent 500 and 600 level parameters, respectively
194 °F
1.3
1.5
1.0
1.8
2.0
2.5
3.5
3.0
176
0.8
158
0.6
140
0.4
122
0.2
104
86 95
Setpoint of the room temperature °F 73 70 66
Outlet temperature
77
50
32
77 68 59 50 41
32 23 14 5 -4 -13 °F
Outdoor temperature
Figure 82 - Reset Slopes
Factory Settings
Parameter
Range
4 Zone 1 4.2 Zone 1 Settings
0 = Fixed Outlet Temperature - Automatic Temperature Control (AUTO) OFF 1 = Basic Temp. Control (without Optional Room Sensor or Outdoor Sensor) 2 = Indoor Temp. Reset (With Optional Room Sensor) 3 = Outdoor Temp. Reset (With Included Outdoor Sensor or weather from the internet if the boiler is connected to WiFi) 4 = Indoor and Outdoor Temp. Reset (With Optional Room Sensor and Included Outdoor Sensor or weather from the internet if the boiler is connected to WiFi)
3
4.2.1 Type of Temperature Control*
The greater the slope, the quicker the boiler target temperature rises as the outdoor temperature decreases. Applicable when 4.2.1 = 3 or 4. Provides a means of adjusting (shifting) the calculated reset boiler target temperature up or down. Applicable when 4.2.1 = 1, 2, 3, or 4. Adjusts the in uence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler target temperature as the indoor temperature drops below room setpoint. Applicable when 4.2.1 = 2 or 4.
4.2.2 Slope of Outdoor Reset Curve 0.2 - 3.5
1.3
-12 to +12 (when 4.2.0 = 0) -25 to +25 (when 4.2.1 = 1)
0
4.2.3 Parallel Shift of Reset Curve
4 ( (when 4.2.0 = 0) 2 (when 4.2.0 = 1)
0 - 20
4.2.4 Room Sensor In uence
Maximum Temperature Setting Minimum Temperature Setting
4.2.5
68-179°F
179
4.2.6
68-179°F
95
4.7 Zone 1 Regulation Parameters
When ON, the boiler automatically adjusts the slope based on the 4.2.2 parameter setting. The slope increases 10% for every 10 minutes a call for heat is active, and decreases 1% every minute after the call for heat has been satis ed.
0 = OFF 1 = ON
4.7.5 Auto Boost
0
Table 29 - Default Parameters for the Heating System Zone 1 - *See the Following Page for Description of 4.2.1
66