NTI INSTALLATION MANUALS

Part 9 - Controls

R. Technical Menu - Complete Menu

Description

Value

Menu

Setting

Default

Sub-Menu

Parameter

ACCESS the Complete Menu

1. Simultaneously press the the OK and ESC buttons for 5 seconds. T he display shows 222. 2. Press the “+” button to select 234 , the service code. 3. Press the OK button. Then press the “+” button until the display shows MENU. 4. Press the OK button to enter the complete menu. See the instructions on page 68 and complete menu list below.

0 NETWORK 0 4 USER INTERFACE

1 = 1 Zone, 2 = 2 Zones, 3 = 3 Zones

0 4 0

Heating zone to be set from the home screen

1

Backlight timing

1 - 10 minutes or 24 hours

10

0 4 1

Reserved for Cascade applications. See Cascade Instruction Manual for details.

Cascade Boiler Con guration

UNDEF = unde ned b-SIN = single boiler b-MAS = master boiler b-FL1 = follower #1 boiler

b-SIN

b-FL2 = Follower #2 b-FL3 = Follower #3 b-FL4 = Follower #4 b-FL5 = Follower #5 b-FL6 = Follower #6, b-FL7 = Follower #7

0 4 6

Units

0 = Metric (°C), 1 = US (°F)

1

0 4 7

2 BOILER PARAMETERS 2 0 GENERAL

DHW Setpoint Temperature TRX COMBI

97 - 140°F

125

Also settable via the home screen - see item 2 Figure 76 (not applicable when 2.2.8 = 2) Enables/disables comfort on/ o setting via COMFORT button and parameter 2.5.0.

2 0 0

DHW Setpoint Temperature TRX non-COMBI

104 - 149°F

125

0 = Disabled 1 = Enabled

2 0 1 DHW Preheating

1

2 1 FREE PARAMETERS (DO NOT USE) 2 1 1 DO NOT USE 2 1 2 DO NOT USE 2 1 3 DO NOT USE 2 1 5 DO NOT USE 2 1 6 DO NOT USE

TRX C models use a ow switch. Not applicable for non-COMBI models.

0 = Flow Switch 1 = Flow Meter

2 1 9

DHW Flow Detection Device Type

0

2 2 BOILER GENERAL SETTINGS 2 2 0 Ignition Power

Must be set in accordance with Table 33.

0 - 100

0 = Auxiliary Limit Switch, 1 = Room thermostat zone 2

2 2 3

TT2 Input Con guration

1

2 2 4

Automatic Temperature Control

0 = Disabled, 1 = Enabled

0

0 = Disabled, 1 = 10 seconds 2 = 90 seconds, 3 = 210 seconds

2 2 5

Heating ignition delay (for new demand)

0

Combi Version - TRX C CANNOT BE MODIFIED

0 = Combi

0

2 2 8

Boiler Version - TRX Type of DHW control for Indirect Hot Water Heater (Tank Sensor or Aquastat)

0 = NOT USED 1 = Storage with Tank Sensor 2 = Storage with Aquastat

2

72

Made with FlippingBook - Online magazine maker