NTI INSTALLATION MANUALS
Part 9 - Controls
R. Technical Menu - Complete Menu
Description
Value
Menu
Setting
Default
Sub-Menu
Parameter
ACCESS the Complete Menu
1. Simultaneously press the the OK and ESC buttons for 5 seconds. T he display shows 222. 2. Press the “+” button to select 234 , the service code. 3. Press the OK button. Then press the “+” button until the display shows MENU. 4. Press the OK button to enter the complete menu. See the instructions on page 68 and complete menu list below.
0 NETWORK 0 4 USER INTERFACE
1 = 1 Zone, 2 = 2 Zones, 3 = 3 Zones
0 4 0
Heating zone to be set from the home screen
1
Backlight timing
1 - 10 minutes or 24 hours
10
0 4 1
Reserved for Cascade applications. See Cascade Instruction Manual for details.
Cascade Boiler Con guration
UNDEF = unde ned b-SIN = single boiler b-MAS = master boiler b-FL1 = follower #1 boiler
b-SIN
b-FL2 = Follower #2 b-FL3 = Follower #3 b-FL4 = Follower #4 b-FL5 = Follower #5 b-FL6 = Follower #6, b-FL7 = Follower #7
0 4 6
Units
0 = Metric (°C), 1 = US (°F)
1
0 4 7
2 BOILER PARAMETERS 2 0 GENERAL
DHW Setpoint Temperature TRX COMBI
97 - 140°F
125
Also settable via the home screen - see item 2 Figure 76 (not applicable when 2.2.8 = 2) Enables/disables comfort on/ o setting via COMFORT button and parameter 2.5.0.
2 0 0
DHW Setpoint Temperature TRX non-COMBI
104 - 149°F
125
0 = Disabled 1 = Enabled
2 0 1 DHW Preheating
1
2 1 FREE PARAMETERS (DO NOT USE) 2 1 1 DO NOT USE 2 1 2 DO NOT USE 2 1 3 DO NOT USE 2 1 5 DO NOT USE 2 1 6 DO NOT USE
TRX C models use a ow switch. Not applicable for non-COMBI models.
0 = Flow Switch 1 = Flow Meter
2 1 9
DHW Flow Detection Device Type
0
2 2 BOILER GENERAL SETTINGS 2 2 0 Ignition Power
Must be set in accordance with Table 33.
0 - 100
0 = Auxiliary Limit Switch, 1 = Room thermostat zone 2
2 2 3
TT2 Input Con guration
1
2 2 4
Automatic Temperature Control
0 = Disabled, 1 = Enabled
0
0 = Disabled, 1 = 10 seconds 2 = 90 seconds, 3 = 210 seconds
2 2 5
Heating ignition delay (for new demand)
0
Combi Version - TRX C CANNOT BE MODIFIED
0 = Combi
0
2 2 8
Boiler Version - TRX Type of DHW control for Indirect Hot Water Heater (Tank Sensor or Aquastat)
0 = NOT USED 1 = Storage with Tank Sensor 2 = Storage with Aquastat
2
72
Made with FlippingBook - Online magazine maker