NTI INSTALLATION MANUALS

Part 9 - Controls

Description

Value

Menu

Setting

Default

Sub-Menu

Parameter

-12 - +12 -25 - +25

Parallel Shift of Reset Curve

0

6 2 3

See description of Parameter 423.

2 if Parameter 6.2.0 = 0 4 if Parameter 6.2.0 = 1

Room Sensor In uence

0 - 20

6 2 4

Adjusts the in uence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler target temperature as the indoor temperature drops below room setpoint. Only applicable when using an optional NTI Room Sensor and when 6.2.1 = 2 or 4. 179 6.2.5 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. 95 6.2.6 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. MAXIMUM temperature setting 68 - 179 °F MINIMUM temperature setting 68 - 179 °F

6 2 5

6 2 6

6 3 DIAGNOSTICS 6 3 0

S/W function activation

0 = OFF, 1 = ON

0 Only applicable when using an NTI room sensor

6 3 1

S/W temperature threshold

50 - 86 °F

68

6 3 4

S/W delay time

0 - 300 minutes

60

6 7 ZONE 3 REGULATION PARAMETERS

See description of Parameter 475.

6 7 5

Auto Boost

0 = OFF, 1 = ON

0

8 SERVICE PARAMETERS 8 0 BOILER STATISTICS-1 - Read Only 8 0 0 3 way valve cycles No. (n x10) 8 0 1 Boiler Pump On Hours (h x10) 8 0 2 Boiler pump cycles No. (n x10) 8 0 3 Boiler Power On Time (h x10) 8 0 4 Fan On Hours (h x10) 8 0 5 Number of fan cycles (n x10) 8 0 6 8 1 BOILER STATISTICS-2 - Read Only 8 1 0 CH Burner On Hours (h x10) 8 1 1 DHW Burner On Hours (h x10) 8 1 2 Number Of Flame Faults (n x10) 8 1 3 Number Of Ignition Cycles (n x10) 8 1 4 Average CH Cycle Length (min) 8 1 6 8 2 BOILER CURRENT STATUS - Read Only 8 2 1 Fan Status 8 0 7

CH number of ame detections (n x10) DHW number of ame detections (n x10)

Number of times the Priority Timer (2.10.4) has elapsed, switching priority from DHW to CH (or vice versa).

0 = OFF, 1 = ON

8 2 2 8 2 3 8 2 4 8 2 5

Fan Speed RPM

Boiler Pump Status 3 Way Valve Position

0 = OFF, 1 or 2 = ON

0 = DHW, 1 = Central Heating

DHW Flow Rate (in US gpm)

Not applicable to these models

8 2 6

APS Status

0 = Open, 1 = Closed

8 2 8 Gas Power (kW) 8 3 BOILER CURRENT TEMPERATURES - Read Only 8 3 0 CH Supply Setpoint (in °F) 8 3 1 CH Supply Temperature (in °F) 8 3 2 CH Return Temperature (in °F) 8 3 3 DHW Outlet Temperature (in °F)

Not applicable to these models

8 3 4

Exhaust Flue Temperature (in °F)

78