NTI INSTALLATION MANUALS
Part 13 - Troubleshooting
Display Error code
Possible cause based on priority
Error Type
Error Description
Possible Remedies
Check the ame sensor and wiring for damage,water or other possible shorts to ground (replace ame sensor).
Blocking (Auto Reset)
Faulty ame sensor
Flame detected out of sequence
5 02
Faulty PCB
If problem persists replace the PCB.
Verify the gas pressure to the appliance while in operation. Ensure pressure is between 3.5 and 10.5”WC (Natural Gas), or between 8 and 13”WC for boilers converted to Propane (LP) operation. Test combustion at high and low re and set it to the high end of the recommended range for the fuel type used.
Improper gas pressure
Improper combustion settings Restricted Air inlet or Exhaust
Check the inlet and exhaust for restriction .
Blocking (Manual Reset)
Flame lost ten times during run
5 04
Dirty combustion chamber or burner
Clean the combustion chamber and burner.
Clean the ame sensor with a mild abrasive or replace the ame sensor.
Dirty /Faulty ame sensor
Blocked condensate drain
Ensure the condensate drain is clear and drains freely.
Inspect ame probe wire for loose connections, shorts to ground or damage. 5P1 may be displayed momentarily if there is a problem the boiler will lock out. Follow the directions for the lockout.
Damaged ame probe cable
5 P1
1st Ignition Failed
Normal operation
Warning
5 P2
2nd ignition attempt failed
See lockout 501.
5 P6
3rd ignition attempt failed
See lockout 501.
In some circumstances the ame will lift during run due to wind.
Wind
Blocked venting
Ensure nothing is obstructing the venting.
Detection of Flame loss during run
5 P3
Warning
If the problem is persistent a lockout will result, follow the trouble shooting for the lockout. If the ame loss is bothersome and does not result in a lockout, see error 504.
Combustion settings or Gas pressure
Air Intake / Exhaust Gas Outlet
Ensure the boiler is free of air and pressurized to a minimum of 18PSI and check that the blue light on the internal pump is on during the heating or hot water demand. Ensure the combustion chamber is cleaned regularly so that ue gas can pass easily. If the error is accompanied by popping or hissing, the boiler my have scale build up preventing proper heat transfer. De scale the heat exchanger if needed. Check fro proper readings from the Flue sensor. Compare it to the reading on parameter 834. If the parameter 834 reading is signi cantly higher ,replace the Flue sensor. Inspect the combustion chamber for damaged or missing refractory replace any damaged or missing components. Check the wiring to the Flue sensor for water or corrosion.
Inadequate water ow
Dirty Combustion chamber
Exhaust Temperature exceeded 204F (the error can only be cleared when the ue temperature drops below 149F)
Water scaling
Blocking (Manual Reset)
6 02
Faulty wiring
Faulty sensor
Missing/ Damaged refractory
clogged condensate drain
Clean the condensate trap ensure its draining freely.
97
Made with FlippingBook - Online magazine maker