NTI INSTALLATION MANUALS
Part 9 - Controls
Description
Value
Menu
Setting
Default
Sub-Menu
Parameter
Determines how much the boiler outlet temperature can go over target before turning the burner o .
4 - 36 o F
CH O Di erential Temperature
11
2 10 5
Anti Water Hammer Function - Combi Version Anti Water Hammer Function - Boiler Version
0 1
0 = OFF, 1 = ON
2 10 6
To disable antifreeze function, set 2.10.7 = 0.
Antifreeze Function
0 = OFF, 1 = ON
1
2 10 7
4 ZONE 1 PARAMETERS 4 0 ZONE 1 TEMPERATURE SETTINGS 4 0 0 Temperature Day
50 - 86 °F 32 - 86 °F 68 - 179 °F 68 - 179 °F
66 Only applicable when using an NTI room sensor
Temperature Night
61
4 0 1
179 Parameter 4.2.0 = 1 120 Parameter 4.2.0 = 0
Zone Fixed Temperature
4 0 2
Only applicable when using an NTI room sensor - Changes all zones
Zone Freeze Protection Temperature
36 - 59 °F
41
4 0 3
4 1 SUMMER/WINTER CHANGEOVER 4 1 0 S/W function activation
0 = OFF, 1 = ON
0
S/W temperature threshold
50 - 86 °F
68
4 1 1
S/W delay time
0 - 300 minutes
60
4 1 2
4 2 ZONE 1 SETTINGS
This parameter determines the starting boiler target temperature when using Basic Temp. Control (4.2.1 = 1)
Temperature Range
0 - 1
1
4 2 0
0 = Fixed Outlet Temperature 1 = Basic Temp. Control 2 = Indoor Temp. Reset 3 = Outdoor Temp. Reset 4 = Indoor and Outdoor Temp. Reset
See Table 29 and F. Type of Temperature Control for details.
Type of Temperature Control
3
4 2 1
Slope of Outdoor Reset Curve
0.2 - 3.5
1.3
194 °F
1.3
1.5
1.0
1.8
2.0
2.5
3.5
3.0
176
0.8
158
The greater the slope, the quicker the target temperature rises as the outdoor temperature decreases. Applicable when 4.2.1 = 3 or 4.
0.6
140
0.4
122
4 2 2
0.2
104
86 95
See J. Slope of Outdoor Reset Curve.
Setpoint of the room temperature °F 73 70 66
Outlet temperature
77
50
32
77 68 59 50 41
32 23 14 5 -4 -13 °F
Outdoor temperature
70