NTI INSTALLATION MANUALS
Part 9 - Controls
Description
Value
Menu
Setting
Default
Sub-Menu
Parameter
-12 - +12 (when 4.2.0 = 0)
See K. Parallel Shift of Reset Curve.
Parallel Shift of Reset Curve
0
-25 - +25 (when 4.2.0 = 1) When the Reset Curve results in a boiler target temperature that is too high or too low (i.e., heats the building too quickly or slowly), Parallel Shift can be used to o set the curve up or down to increase or decrease the boiler target temperature.
NOTE: Adjusting Parallel Shift is only possible when Auto Boost is OFF (4.7.5 = 0).
The Parallel Shift can be adjusted from the home screen using the CH + and - buttons (Figure 59, Item 8).
4 2 3
With the rst press of the CH + or - button, the display shows the current CH target temperature (e.g., 130 o F).
1
AUTO
After a 3-5 second delay, the display begins ashing the current o set (Parallel Shift) setting. Subsequent CH + or - button presses adjusts the o set up or down.
After a few seconds the display shows the new CH target temperature (e.g., 138 o F), then returns to the home screen.
2 if Parameter 4.2.0 = 0 4 if Parameter 4.2.0 = 1
Room Sensor In uence
0 - 20
4 2 4
Adjusts the in uence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler target temperature as the indoor temperature drops below room setpoint. Only applicable when using an optional NTI Room Sensor and when 4.2.1 = 2 or 4. 179 4.2.5 sets the allowable boiler operating temperature range for Zone 1 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. 95 4.2.6 sets the allowable boiler operating temperature range for Zone 1 heating, limiting Automatic Temperature Control and manual adjustments from the User Menu. MAXIMUM Temperature Setting 68 - 179 °F MINIMUM Temperature Setting 68 - 179 °F
4 2 5
4 2 6
4 3 ZONE 1 DIAGNOSTICS 4 3 0 Room Temperature
Read only Read only
Only applicable when using an NTI room sensor
Room Temperature Setpoint
4 3 1 4 3 4
Heat Call
0 = OFF, 1 = ON (Read only)
4 7 ZONE 1 REGULATION PARAMETERS 4 7 5 Auto Boost 5 ZONE 2 PARAMETERS 5 0 ZONE 2 TEMPERATURE SETTINGS 5 0 0 Temperature Day
0 = OFF, 1 = ON
0 See L. Auto Boost.
50 - 86 °F 32 - 86 °F 68 - 179 °F 68 - 179 °F
66 Only applicable when using an NTI room sensor
Temperature Night
61
5 0 1
179 Parameter 5.2.0 = 1 120 Parameter 5.2.0 = 0
Fixed Temperature
5 0 2
Only applicable when using an NTI room sensor - Changes all zones
Zone Freeze Protection Temperature
36 - 59 °F
41
5 0 3
5 1 SUMMER/WINTER CHANGEOVER 5 1 0 S/W function activation
0 = OFF, 1 = ON
0
S/W temperature threshold
50 - 86 °F
68
5 1 1
S/W delay time
0 - 300 minutes
60
5 1 2
5 2 ZONE 2 SETTINGS
This parameter determines the starting boiler target temperature when using Basic Temp. Control (5.2.1 = 1)
Temperature Range
0 - 1
1
5 2 0
71